Optimalisasi Kualitas Kenyamanan Thermal di Ruang Kantor dan Aula Islamic Centre UIN SUSKA Riau
Abstract: Energy conservation
in buildings is a serious attention in Indonesia, including as one of the focus
in the Roadmap Research, Development, and Application of Science and Technology
Field of New and Renewable Energy Sources from the Ministry of Research and
Technology. This study aims to determine the thermal calculator PMV” provided
by Luma Sense Technologies to get the value of PMV-PPD and thermal comfort
employee feels comfortable with the PMV value of 0.7 (slightly warm) and PPD
value of 16.89 (mean 16.89% of people feel uncomfortable in the room), but when
the air conditioner off at 12.00 am, the PMV value rose to 2.76 (Hot) and PPD
96.57 (mean 96.57% of people feel uncomfortable). As for the condition of the
hall with AC On the value of PMV = 1.8 (warm), PPD value of 67.89 (mean 67.89%
of people feel uncomfortable), and so the AC off at 12.00 pm, the PMV value
rose to 3.1 (Hot) with PPD 99, 5 (mean everyone does not feel of State Islamic
University of Suska Riau at Islamic center relies heavily on the use of air
conditioning, so the AC Off the thermal comfort is reduced drastically,
especially in the middle of the day and hot weather during the term of the
study. Based on the analysis and discussion of design concepts found most
appropriate to the condition of the building with the addition of the IC is the
insulation of the building, with one of the alternative types of polyurethane
foam insulation is spray applied a simple and practical and appropriate for
buildings that have been standing.