UJI EKSPERIMENTAL MESIN PENDINGIN BERPENDINGIN AIR DENGAN MENGGUNAKAN REFRIGERAN R22 DAN REFRIGERAN R407C

Abstract: The human needs of refrigeration system have created a tool that called a refrigerator. Refrigerator/cooling machine have a component which have a very important role in the refrigerationsystem that is refrigerant. Refrigerant that still widely used for cooling machine until now is the refrigerant R22. Using R22 refrigerant can cause environmental problems such as damage to the ozone layer and global warming. Therefore, it needs a substitution refrigerant which is more friendly forenvironment which one of them is R407C refrigerant. In this study, using a cooling machine with watercooled condenser and the flowrate that use is 20 L/h, 40 L/h, 80 L/h and 120 L/h. The variables that measured in this study is temperature (T1, T2, T3, T4, T10, T11), pressure (P1, P2, P3, P4), and ampere. Thisstudy aims to get the test results using refrigerants R22 and R407C. The processing data of the test result include refrigeration capacity, compressor power and COP. The results obtained have that cooling machine which use R22 refrigerants have a better COP than using R407C refrigerant. This is happen because the power needed by the compressor to compress R407C refrigerant to flow in the system is greater than using R22 refrigerant.
Keyword: Refrigeration system, cooling machine, refrigerant, water-cooled condenser