EFEKTIVITAS PENGGUNAAN THERMOSTATIC EXPANTION VALVE PADA REFRIGERASI AC SPLIT
Abstract: Vapor compression
refrigeration is one of refrigeration systems that is most widely used for the
cooling process in a variety of human needs. In this type of machine there is a
component that can be varied kind, namely the expansion valve, such as a capillary
tube and thermostatic expansion valve (TXV). Experimental tests have been
conducted in a one HP split air conditioning refrigeration machine capacity to
compare the performances between the use of a capillary tube and TXV expansion
valve. The experimental results show that
the use of a capillary tube responds to the greater cooling load of the smaller
COP, COP highest achieved in the condition of the refrigerant out of the
evaporator in the form of vapor saturated with COP = 5.3. While the use of TXV,
COP value increases with the addition of the cooling load. The highest COP
achieved is 5.87.